Chris, there has been many a foreign 'electrician' in Thailand who did not apply the correct application of electrical installations in Thailand.
Whilst what I'm saying MAY be equivalent to 'losing face' for the foreign electrician, this is no excuse for an incorrect electrical installation.
In any situation, the first thing that MUST be determined is the 'Earthing System'.
Is it IT,TT or TN?
If it is IT, RCD's MUST be used on every circuit, since Thailand does legislate IMD's (Insulation Monitoring Devices) for IT systems. This is the only way to ensure some form of safety with this system. Also, RCD's are electronic devices & can easily fail (storms etc). This means that RCD's used within an IT installation (or ANY installation) MUST be checked AT LEAST every month by pressing the 'test' button.
A TT installation requires a somewhat different approach.
All cabling (wiring) from appliances back to the consumer unit, must NOT exceed certain ohmic values as well as the circuit breaker(s) MUST be correctly sized according to 'trip times'. This will ensure that the circuit breaker (not RCD) will trip in the appropriate amount of time, which is a minimum of 0.4 seconds for any fault.
For this reason, 'Earth Fault Loop Impedance' tests are carried out, which 'prove' that circuit breakers CAN trip in less than 0.4 seconds, under possible fault conditions.
In a proven TN (C+S) system, the 'Main Neutral' can be connected to the 'Main Earth Bar' in the consumer unit, which will greatly help the operating speed of circuit breakers but is VERY dependant on 'polarity'.
In Thailand, the PEA have published a document (in Thai), which I translated.
The document essentially said how a domestic installation should be wired. According to their document, it should be wired according to a TN (C+S) earthing system.
The contradiction is that many new installations are according to the IT earthing system in suburban Thailand. The practice of the PEA compared to THEIR published document proves that they DO NOT care about or monitor electrical safety.
As a result, it is HIGHLY recommended that RCD's be used on EVERY circuit in Thailand.
I would suggest that if Cambodia has the same approach, RCD's MUST be used on EVERY circuit to ensure electrical safety.
BTW, 'earthing' does not matter in IT installations.
In any other installation, it DOES matter. The way that correct 'earthing' is implemeted is according to the 'know how' of the electrician & his/her ability to establish which 'earthing system' is used.
Also, there is no such thing as a 'legislated' Thai Electrical Code. The closest thing to this is a book, in Thai, called the Thai Electrical Code. This book was written by the EIT (Engineering Institute of Thailand).
Here is a link to this amazing book, which is in Thai.
Google Translate