Page 3 of 7 FirstFirst 1234567 LastLast
Results 51 to 75 of 153
  1. #51
    Thailand Expat terry57's Avatar
    Join Date
    Mar 2007
    Last Online
    07-12-2022 @ 03:12 PM
    Posts
    26,746
    ^

    Lack of a proper Earth no doubt and a dodgy install.

  2. #52
    Thailand Expat Pragmatic's Avatar
    Join Date
    Mar 2013
    Last Online
    @
    Location
    Last but who gives a shit.
    Posts
    13,420
    Quote Originally Posted by beerlaodrinker
    I seem to recall a couple of tourists getting electrocuted in the swimming pool a while ago. Shitty wiring? Somchai strikes again.
    There was a tourist killed in Pattaya a few years back whilst walking through a puddle in the road. https://teakdoor.com/thailand-and-asi...trocution.html

  3. #53
    Member

    Join Date
    Oct 2011
    Last Online
    04-04-2018 @ 09:53 AM
    Posts
    655
    Quote Originally Posted by terry57 View Post
    Actually further more,

    There are some qualified Electricians on this forum, I'd love to hear their take on the 10MM cabling to the friggin kitchen oven.
    This is the correct size for the load and run distance.

  4. #54
    Member

    Join Date
    Oct 2011
    Last Online
    04-04-2018 @ 09:53 AM
    Posts
    655
    Quote Originally Posted by terry57 View Post
    Quote Originally Posted by thailazer View Post

    Nothing wrong with that at all.

    I bet he is not worried at all about voltage drop in the wiring when he has his oven, coffee pot, and toaster all going at the same time. Kitchen appliances can add up to a lot of current.

    The only problem with large conductors like that is that they are difficult to pull through conduit.
    Mate, seriously,

    If you are a qualified Electrician and you are telling me that using 10 mm twin and earth cable to wire a standard house is a good idea I suggest you go back to Electrical school.

    If volt drop is the problem the correct way to do it would be to use the 10 mm as the run in from the power source to the house and then wire the house with the correct size cabling, that being 2.5mm twin and earth for the power and 1.5 mm for the lighting circuit.

    Jesus, where is Baldrick ?

    He is the electrical expert on this forum and will put this stuff to bed in 2 seconds.

    10 MM wire for a standard house install.
    bolliks.

    Using 2.5 mm power cable is sufficient enough to run every house hold appliance 24/7 without any problem what so ever as long as the house and appliances are wired correctly and the correct voltage is being delivered to the house.

    If the correct voltage is not being delivered to the house it would not matter if one used 50mm within the house, the system will not operate correctly.
    2,5 is too small for showers ovens etc etc, what mud hut do you live in?

  5. #55
    Thailand Expat

    Join Date
    Mar 2011
    Last Online
    25-03-2021 @ 08:47 AM
    Posts
    36,437
    Heh...Here we go...

  6. #56
    Thailand Expat terry57's Avatar
    Join Date
    Mar 2007
    Last Online
    07-12-2022 @ 03:12 PM
    Posts
    26,746
    ^



    Forget to allow for trolls. Oh well play on.

  7. #57
    Thailand Expat

    Join Date
    Mar 2011
    Last Online
    25-03-2021 @ 08:47 AM
    Posts
    36,437
    ^Where's Baldrick?...

  8. #58
    Thailand Expat terry57's Avatar
    Join Date
    Mar 2007
    Last Online
    07-12-2022 @ 03:12 PM
    Posts
    26,746
    ^

    Unfortunately any thread where I am Baldick steers well clear off.

    Baldick don't like me very much, Actually I feel it goes much deeper.

    Oh well, such is forum life Heh.

    Bit of a bummer in this situation, one can never question his Electrical knowledge.

    Foker gets paid squillions for his knowledge.

  9. #59
    Thailand Expat

    Join Date
    Mar 2011
    Last Online
    25-03-2021 @ 08:47 AM
    Posts
    36,437
    Quote Originally Posted by terry57
    Oh well, such is forum life Heh.
    No shit...Well, maybe he'll make his way over and add his two bits...

  10. #60
    Excommunicated baldrick's Avatar
    Join Date
    Apr 2006
    Last Online
    Today @ 02:55 PM
    Posts
    24,865
    Quote Originally Posted by BaitongBoy
    ^Where's Baldrick?...
    fondling my turnips - have a fiddle with this

    Cablesizer | Cable Sizing Calculations to IEC and NEC Standards

  11. #61
    . Neverna's Avatar
    Join Date
    Mar 2012
    Last Online
    @
    Posts
    21,385
    Quote Originally Posted by baldrick View Post
    fondling my turnips - have a fiddle with this

    Cablesizer | Cable Sizing Calculations to IEC and NEC Standards
    240V, single phase, copper conductors, 6kw load, 25 C ambient temperature ...

    "The minimum Single Core cable size is: 10.0 mm2"
    "The minimum Multi Core cable size is: 10.0 mm2"


    *Same for 20C ambient temperature, same for 220V, same for single core cables, same for multi-core cables.
    Last edited by Neverna; 25-02-2015 at 05:46 PM.

  12. #62
    Thailand Expat
    Join Date
    Jun 2014
    Last Online
    @
    Posts
    18,022
    Quote Originally Posted by beerlaodrinker View Post
    I seem to recall a couple of tourists getting electrocuted in the swimming pool a while ago. Shitty wiring? Somchai strikes again.
    Subtle, but effective.....


  13. #63
    Thailand Expat terry57's Avatar
    Join Date
    Mar 2007
    Last Online
    07-12-2022 @ 03:12 PM
    Posts
    26,746
    Quote Originally Posted by baldrick View Post

    fondling my turnips - have a fiddle with this

    Cablesizer | Cable Sizing Calculations to IEC and NEC Standards
    Urm,

    Thanks for that but I cannot remember the figures to enter in.


    I'll just rely on what the Tradesman taught me when I wired up the hundreds of houses I have done.

    Never used 10MM in any of them.

    Of course not as its fookin not done on residential domestic installs.

    Good troll though.

  14. #64
    Thailand Expat
    Gazza's Avatar
    Join Date
    Mar 2006
    Last Online
    @
    Location
    Wat Thafookhisit near to Wat Chamakhorlit
    Posts
    2,314
    Quote Originally Posted by terry57
    Jesus, where is Baldrick ?
    He is the electrical expert on this forum and will put this stuff to bed in 2 seconds.
    Quote Originally Posted by BaitongBoy
    Where's Baldrick?...
    Quote Originally Posted by terry57
    one can never question his Electrical knowledge.

    Foker gets paid squillions for his knowledge.
    Amid the quietened halls of the forum an audience gathered, awaiting with bated breath for the 'Seer of Circuitry', the 'Wizard of Wiring', the 'Sage of Surge' to appear offering divine assistance.

    The 'Warlock of Wattage' finally emerges in all his splendour, scratching his nether regions and shatters the silence created by his neophytes with.......

    fondling my turnips - have a fiddle with this
    Cablesizer | Cable Sizing Calculations to IEC and NEC Standards
    And thus spake 'baldrick'.


  15. #65
    . Neverna's Avatar
    Join Date
    Mar 2012
    Last Online
    @
    Posts
    21,385
    And thus spake 'baldrick'....


    only to be greeted by Terry57 with ..

    Quote Originally Posted by terry57 View Post
    Good troll though.
    Is Terry57 questioning Baldrick's electrical knowledge, his expertise, or just the link he provided? Who's the troll Terry?

  16. #66
    cnx37
    Guest
    Best option - just ignore Terry in all ways. Problem solved. Then there is no problem.

  17. #67
    Thailand Expat
    Iceman123's Avatar
    Join Date
    Aug 2013
    Last Online
    Yesterday @ 10:03 PM
    Location
    South Australia
    Posts
    5,558
    Terry is obviously not wired up right.

  18. #68
    Thailand Expat

    Join Date
    Mar 2011
    Last Online
    25-03-2021 @ 08:47 AM
    Posts
    36,437
    ^Thanks for your valuable input AnalAndy...Now charge up your buttplug with 10mm wiring and fck off...

  19. #69
    . Neverna's Avatar
    Join Date
    Mar 2012
    Last Online
    @
    Posts
    21,385
    240V, single phase, copper conductors, 6kw load
    "The minimum Single Core cable size is: 10.0 mm2"
    "The minimum Multi Core cable size is: 10.0 mm2"
    *Same for 20C ambient temperature, same for 220V, same for single core cables, same for multi-core cables.

    240V, single phase, copper conductors, 5kw load
    "The minimum Multi Core cable size is: 6.0 mm2"

    240V, single phase, copper conductors, 4kw load
    "The minimum Multi Core cable size is: 4.0 mm2"

    240V, single phase, copper conductors, 3kw load
    "The minimum Multi Core cable size is: 2.5 mm2"


    So, we can gather from this thread that Australians in Perth only use 3kw shower units - or Perth sparkies don't shower at all.

    You are welcome, Terry.

  20. #70
    cnx37
    Guest
    Quote Originally Posted by Neverna View Post

    So, we can gather from this thread that Australians in Perth only use 3kw shower units - or Perth sparkies don't shower at all.

    You are welcome, Terry.
    That is excellent observation & thorough logic, Sherlock.

  21. #71
    Thailand Expat

    Join Date
    Mar 2011
    Last Online
    25-03-2021 @ 08:47 AM
    Posts
    36,437
    ^Nice new av there, cnx...People look at you in a new light, now...

    Well done...

  22. #72
    Thailand Expat

    Join Date
    Feb 2010
    Last Online
    14-05-2017 @ 03:18 AM
    Posts
    1,031
    Quote Originally Posted by crippen View Post
    Quote Originally Posted by Pragmatic View Post
    Quote Originally Posted by crippen
    While on this electric stuff,why is the neutral in Thailand not earthed???
    I know the answer to that 100% for sure. In Thailand the neutral carries a voltage of 2-3 volts. Connecting it to your earth will give you a mild shock if your shower is earthed and you touch any of the metal parts of the shower. You DO NOT connect your neutral to earth in Thailand.
    Our phase went off recently (transformer blew up !). The fans just ran a bit slower,the tv still worked ok. Confused me until I found there was 75 volts on the neutral to earth. Go figure.
    (If the UK wiring regs are so brilliant,why are we now on issue 16,or is it 17 now????
    It was because of 'back feed' on a three phase line. One phase goes out but the remaining two phases 'back feed' through another three phase transformer bank, albeit at a lower voltage.

  23. #73
    Thailand Expat

    Join Date
    Feb 2010
    Last Online
    14-05-2017 @ 03:18 AM
    Posts
    1,031
    Quote Originally Posted by mykthemin View Post
    Quote Originally Posted by terry57 View Post
    Quote Originally Posted by thailazer View Post

    Nothing wrong with that at all.

    I bet he is not worried at all about voltage drop in the wiring when he has his oven, coffee pot, and toaster all going at the same time. Kitchen appliances can add up to a lot of current.

    The only problem with large conductors like that is that they are difficult to pull through conduit.
    Mate, seriously,

    If you are a qualified Electrician and you are telling me that using 10 mm twin and earth cable to wire a standard house is a good idea I suggest you go back to Electrical school.

    If volt drop is the problem the correct way to do it would be to use the 10 mm as the run in from the power source to the house and then wire the house with the correct size cabling, that being 2.5mm twin and earth for the power and 1.5 mm for the lighting circuit.

    Jesus, where is Baldrick ?

    He is the electrical expert on this forum and will put this stuff to bed in 2 seconds.

    10 MM wire for a standard house install.
    bolliks.

    Using 2.5 mm power cable is sufficient enough to run every house hold appliance 24/7 without any problem what so ever as long as the house and appliances are wired correctly and the correct voltage is being delivered to the house.

    If the correct voltage is not being delivered to the house it would not matter if one used 50mm within the house, the system will not operate correctly.
    2,5 is too small for showers ovens etc etc, what mud hut do you live in?
    Residential houses have more than one circuit. 2.5 mm is fine for a lighting circuit.

    A water heater would require a larger wire size, American Wire Gauge #12 or 3.31 MM according to the chart I referenced.

    Guys that say the entire house should be wired with 10MM have never had to work with that size wire in an outlet box.

    No can do...

    10 MM would be enough for the entrance cable for many residential houses in Thailand. Sub circuits are sized according to the load.

    Ohms Law. P= E* I. Power = Voltage * Current
    Last edited by Lancelot; 26-02-2015 at 07:18 AM.

  24. #74
    Thailand Expat
    crepitas's Avatar
    Join Date
    Apr 2013
    Last Online
    27-03-2017 @ 08:11 AM
    Posts
    1,964
    Quote Originally Posted by terry57 View Post
    Today I visited Klong Toeh head Office Electrical Department Bangkok.

    On display they had a complete wiring diagram for a house.

    It was spot on, Exactly how things would be done in the real world.

    Power points, water heater and Air Con all wired in the correct sized cable, that being 2.5 ML twin and Earth.

    Lights wired in 1.5 Ml and the main Earth wired to the Earth Spike.

    I could not establish if the 1.5 Ml light cable had an earth.

    In the real world this is a must.

    Anyway, if one wants Electrical work done properly go to the Government approved office and not Somchai the Back yarder.

    Thailand does has correct standards if the proper people are sourced.

    Up to You.
    Somewhat ironic that the new install inspection team of two from PEA...walked in our house looked at the service box without opening it,asked if we had a ground and a GFI, nodded and left.
    Still don't understand why so many appliances come with Schuko plugs....defeats the object of grounding..never seen any outlets available?

  25. #75
    Thailand Expat
    crepitas's Avatar
    Join Date
    Apr 2013
    Last Online
    27-03-2017 @ 08:11 AM
    Posts
    1,964
    On the ongoing debatable subject of grounding and or ground to neutral bonding:
    While a grounded appliance offers protection against fire, it is not a guaranteed protection against electrical shock. In the event of an insulation breakdown or similar fault, unless sufficient current is leaking to fire a 15 amp or perhaps more breaker the appliance will still be live.
    Only sure protection is a leakage protection breaker (Safety Cut or). Whole house plus individual separate units for pumps and shower heaters.
    I wired our house and bonded ground to neutral..Good idea?..Not sure since, as one poster pointed out, your house could become the defacto return for your neighborhood in the event the ground/neutral in the network fails.

Page 3 of 7 FirstFirst 1234567 LastLast

Thread Information

Users Browsing this Thread

There are currently 1 users browsing this thread. (0 members and 1 guests)

Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •